FLOATING FLOOR UNDERLAY
Field of the Invention
This invention relates to floating floor systems. More
particularly, this invention relates to a floating floor underlay product
and method of installing a floating floor over a subfloor.
Background of the Invention
Products installed on top of a subfloor and under a floor
treatment that aid in the floor treatment's installation are known in the
art. Often, it is desirable to prevent a floor treatment from absorbing
moisture that seeps up through a subfloor that may cause a floor
treatment to degrade or swell, potentially causing the flooring to
buckle to lift away from the subfloor, causing, for example, premature
glue-joint failure. A problem associated with prior art underlays
applied between the floor treatment and subfloor is that their
installation tends to be overly complicated and difficult. One example
of a known underlay product uses a layer of low density thermoplastic
foam applied over a subfloor. This foam is generally porous and
allows moisture to seep up through the foam and contact the floor
treatment, which may thereby damage the floor treatment in the
manner mentioned above. In order to prevent this problem, a second
layer of thermoplastic film must be installed over the layer of foam to
act as a moisture barrier. The foam layer and the film layer tend to
shift and fold during installation and must be adhesively tacked both
together and to the subfloor so that shifting or folding is minimized
when laying the floor treatment. Also, the low density foam used in
this system allows vertical impacts, e.g., foot falls, to resonate and be
amplified through the floor treatment where the treatment is laminate
wood flooring, for example, resulting in an undesirably loud floor
installation.
Another underlay system uses a compressed rigid
fiberboard in conjunction with a thermoplastic layer. The fiberboard is
directly applied to a subfloor in small sheets. Small sheets of the rigid
fiberboard installed side by side result in a large number of joints in
the assembled underlay which must be sealed. The large number of
joints to be sealed increases the probability of premature joint failure
from repeated foot falls to the joints since the rigid fiberboard sheets
tend not to give but, rather, to separate relative to each other. As
with the above example, in order to make this underlay moisture
impermeable, a thermoplastic film must be adhesively tacked to the
fiberboard . The fiberboard and film assembly degrades and literally
falls apart over time due to repeated vertical impacts to the floor
treatment, i.e., walking over the floor. Once the fiberboard fails, a
soft spot is created under the floor treatment which leads to an
uneven surface and, ultimately, failure of the floor treatment above
the degraded underlay region . This construction is also susceptible to
amplifying the sound of foot falls.
Certain foams are unsuitable for use as flooring underlay.
For instance, a polyethylene foam is a closed cell foam, the closed
cells being under slightly positive pressure from the physical blowing
agent captured therein, formed during the foaming process. The
closed cells are what give the foamed product its resiliency and much
of its thickness. If the foam cells are ruptured, the foam loses its
resiliency and thickness and creates a dead spot in the foam that
leads to degradation of the floor treatment, and increased noise as
mentioned above.
Objectives of the Invention
It has therefore been an object of the present invention
to provide an underlay for a floating floor that facilitates floating floor
installation without bunching, folding, or sliding of the underlay
product before or during installation of the floating floor.
Another object of the present invention is to provide a
thin underlay for a floating floor with acoustic damping characteristics
superior to those of the prior art in a one piece composite that resists
bunching, folding, or sliding prior to or during installation of the
floating floor.
It is another object of the present invention to provide a
method of installing a floating floor over a subfloor.
Summary of The Invention
The objectives of the present invention are achieved by
providing in the preferred embodiment a composite underlay product
for a floating floor made from a moisture impermeable vinyl film to
which an open cell latex foam is directly cast. The open cell latex
foam allows lateral and vertical moisture transmission therethrough.
As used herein, the vinyl film creates a moisture impermeable
underlay when laid over a subfloor and under a floating floor and
seams created between abutting sheets of underlay are sealed with
moisture impermeable tape.
The latex foam surface of the composite underlay has a
relatively high coefficient of friction between itself and a subfloor so
that when placed against the subfloor prior to installation of a floating
floor, the underlay grips the subfloor and does not shift and fold . The
vinyl film surface of the composite underlay has a relatively low
coefficient of friction between itself and a floating floor so that when
the floating floor is installed against this film surface of the underlay,
the floating floor easily slides over the film surface, preventing
bunching of the composite underlay. Because the film is permanently
cohered to the foam, no bunching or separation occurs between the
two components of the underlay during installation or use.
The underlay of the present invention is thin, dense and
soft producing low durometer readings on the Shore 00 Scale. This
combination acts as an efficient acoustic dampener to absorb noise
created by foot falls transmitted through the floating floor and also
absorbs more kinetic energy than polyethylene foam underlays. The
latex foam is of open cellular structure. As a result, the underlay does
not lose its resiliency and will not degrade beneath a floating floor
over time due to repeated vertical impacts, thereby prolonging the life
of the floating floor.
Also contemplated is a method for installing the underlay
between the subfloor and the floating floor, wherein the subfloor is
cleaned of debris, the foam surface of the underlay is placed against
the subfloor and position the floating floor onto the film layer of the
underlay. Seams formed between strips of underlay are optionally
taped .
Brief Description of the Drawings
Fig . 1 is a partially cutaway perspective view of the
installation of a floating floor according to the present inventive
system;
Fig . 2 is a cross section of Fig . 1 taken along line 2-2;
and
Fig . 3 is a close-up view of the cross section of Fig. 2
showing an alternative embodiment of the underlay.
Detailed Description of the Preferred Embodiment
As is seen generally in Figs. 1 -3, in the preferred
embodiment of the present inventive system 10 for installing a
floating floor 1 5 over a subfloor 1 4, an underlay 1 2 is laid over the
subfloor 1 4 made of concrete, wood, or other materials common in
subfloor construction. The floating floor 1 5, e.g., vinyl flooring,
modular wood flooring and the like, is thereafter placed against the
underlay 1 2.
The underlay 1 2 is a composite of a moisture
impermeable film 1 8 cohered to an open-celled foam 20. As will be
understood herein, the term "cohered" means any suitable process
known in the art to permanently join the film 1 8 to the foam 20,
including, for example, direct casting and laminating. As will be
understood herein, the term "moisture impermeable" means a water
transmission value of less than .007 oz/yd2/hr (239 mg/m2/hr) . In the
preferred embodiment, the film 1 8 is polyvinylchloride or
polyurethane. However, other moisture impermeable polymer films
may be used, e.g ., polyethylene, polypropylene. In order to be
moisture impermeable, the thickness of the film 1 8 used is important.
The film 1 8 should be no less than 0.002 inches (0.005 cm) thick,
with a preferred range of about 0.002 inches (0.005 cm) to about
0.008 inches (0.02 cm) thick, and have a weight in the range of
about 2.0 oz/yd2 (67.5 g/m2) to about 8.0 oz/yd2 (269.9 g/m2) .
In the preferred embodiment, the film 1 8 is manufactured
by calendaring . As will be understood by those in the art, the film 1 8
may be manufactured by any other suitable process, e.g ., extrusion
and blowing.
In the preferred embodiment, the foam 20 is an open-
celled, mechanically frothed expanded latex foam. As will be
understood herein, the term "open-celled" means having the
characteristic property of allowing air or moisture to pass
therethrough. In the preferred embodiment, the foam 20 has a
density greater than 1 0 lb/ftJ ( 1 60.2 kg/m3), with a preferred range of
about 1 1 to about 1 5 lb/ft3 ( 1 76.2 to 240.28 kg/m3) . Also in the
preferred embodiment, the foam 20 has a thickness in the range of
about 0.045 inches to about 0. 1 inches (0.1 1 cm to 0.25 cm), with a
preferred thickness of 0.075 inches (0.1 9 cm) . Because the foam 20
is open celled, the underlay 1 2 allows moisture to travel both laterally
and vertically therethrough. In order to make the underlay 1 2
moisture impermeable when installed under a floating floor 1 5, seams
30 between abutting strips of underlay 1 2 must be sealed, as
discussed further below.
As can be seen in Table 1 , samples of a latex foam in
accordance with the principles of the present invention have a much
lower average durometer value on the Shore 00 Scale when
compared to samples of closed cell polyethylene foam over thirty-six
runs. Also, the latex foam samples in Table 1 have a much higher
density (1 1 .23 lb/ft3) ( 1 79.9 kg/m3), than the polyethylene foam
samples (2.1 1 lb/ft3) (33.8 kg/m3) , tested above. This combination of
lower durometer value and higher density relative to closed cell
polyethylene foam imparts desirable sound damping characteristics to
the latex foam when used as a component of an underlay. Thus, a
thin, pliable and soft, yet relatively dense latex foam 20 has sound
damping characteristics that tend to muffle and deaden typical low
frequency acoustic energy generated by walking over an un-
dampened floating floor as is discussed further below. Open-celled
polyvinylchloride and polyurethane foams may also be used in the
underlay 1 2 in place of the latex foam 20.
Table 2 shows results of three separate tests performed
to measure the sound emitted from a golf ball dropped onto a floating
floor surface with no underlay, a polyethylene foam underlay and a
latex foam underlay in accordance with the present invention, from a
height of 1 2 inches. The test was performed with Extech Instruments
407736 sound level meter conforming to IEC 651 , ANSI S1 .4 TYPE 2
at 1 8 inches from the point of impact. The floating floor was placed
over a concrete subfloor. The sound level meter was placed 1 8
inches from the intended impact of the golf ball off of, but
immediately adjacent to an edge of the floating floor measuring sound
resonating through the floating floor. The sound level meter was set
to detect and hold the maximum sound level emitted by the floating
floor when the golf ball was dropped thereon. This was repeated
twenty times for each of the floating floor with no underlay, floating
floor with polyethylene foam underlay, and floating floor with latex
foam underlay. As seen in Table 2, the values of the same floating
floor with no underlay, polyethylene underlay, and a latex foam
underlay in accordance with the present invention are compared. A
nearly 3dB average reduction in sound intensity is achieved by the
latex foam underlay over no underlay and a nearly 2.5 dB reduction
over the polyethylene underlay.
As is seen in Table 3, a latex foam underlay in
accordance with the present invention absorbs kinetic energy better
than a polyethylene foam underlay. In order to test the kinetic energy
absorption of a latex foam underlay in accordance with the present
invention compared to the kinetic energy absorption of a polyethylene
foam underlay, a golf ball was first dropped from an elevated surface
of constant height onto a concrete subfloor and its rebound height
from the subfloor is recorded to achieve a baseline value for the golf
ball's rebound. This procedure is repeated a number of times in order
to calculate a baseline average value of kinetic energy absorbed of
the golf ball bouncing off the baseline target for comparison to the
amount of kinetic energy absorbed by each underlay product.
Next, different thicknesses of each underlay product
were placed on the subfloor, each thickness of each underlay being
subjected to the same number of golf ball drops. The average
rebound of the golf ball from each thickness of each underlay was
measured .
Each time the golf ball is dropped from the constant
height onto the subfloor, latex foam underlay target and polyethylene
foam underlay target, the ball has a first potential energy prior to
being dropped. At the top of the ball's rebound from each of the
aforementioned respective surfaces, the ball, at its rebound apex, has
a second potential energy. The ball's second potential energy when
rebounding from the respective underlays was compared with the
second potential energy of the golf ball rebounding from the subfloor,
and the difference therebetween represents the kinetic energy
absorbed by the latex foam and polyethylene foam underlays.
The latex foam underlay tested had a density of 1 1 .8
lb/ft3 ( 1 89.0 kg/m3), and the polyethylene foam underlay tested had a
density of 2.1 lb/ft3 (33.6 kg/m3) . The test was performed by
dropping a golf ball onto various thickness of each underlay from a
height of 37.5 inches (93.5 cm) . Various thicknesses were used to
eliminate the tendency for the underlays to "bottom out" under
impact. The rebound height of the golf ball from each underlay was
recorded and the percentages of kinetic energy absorbed was
calculated by comparing the second potential energy from the golf
ball rebound off each underlay to the potential energy of the golf ball
at its rebound apex when dropped onto the subfloor. This is a test to
determine the ability of each product to absorb and distribute energy
within the product. The latex foam underlay absorbed, on average,
almost three times as much kinetic energy as the polyethylene foam
underlay of the same thickness, as seen in Table 3.
TABLE 1
Laminate Floor Underlay Hardness Comparison
Shore 00 Durometer Scale
TABLE 2 Drop Test Sound Intensity Comparison
Average vs no underlay vs PE underlay
TABLE 3 Kinetic Energy Absorption Comparison
In the preferred embodiment, the foam 20 is directly cast
to the film 1 8, by a process known in the art. It will be understood
by those in the art that the foam 20 and the film 1 8 components also
may be cohered together by any suitable process known in the art,
e.g ., adhesively bonding, or laminating the foam 20 and film 1 8
components together.
In an alternative embodiment (Fig . 3) , the foam 20 is
cohered to a carrier 22, e.g ., a polymer textile, for example, a spun-
cast, extruded or carded needle-punched homopolymer or a
copolymer of polyester, polypropylene, polyethylene, polyolefin,
polyamide or acrylic material or other woven or knitted natural fibers
to create a substrate composite 24. The foam 20 is cohered to the
carrier 22 by any suitable process known in the art. In the preferred
embodiment, the carrier 22 has a thickness in the range of about
0.006 inches (0.01 5 cm) to about 0.025 inches (0.06 cm) and has a
weight in the range of about 0.4 ( 1 3.6 g/m2) to about 2.0 oz/yd2
(67.8 g/m2) . The film 1 8 is then cohered to the substrate composite
24 by any suitable process known in the art.
The underlay 1 2 of both embodiments has a first face 26
comprised of the film 1 8 and a second face 28 comprised of the foam
20. In the preferred embodiment of the system 1 0, the second face
28 has a coefficient of friction greater than 0.8 between itself and the
subfloor 1 4, so that when the second face 28 is installed against the
subfloor 1 4, the friction between the subfloor 1 4 and the second face
28 prevents slipping and bunching relative to each other. While the
coefficient of friction of the second face 28 is greater than 0.8
between itself and the subfloor 1 4, in the preferred embodiment, the
material from which the subfloor 1 4 is made determines how high the
coefficient of friction of the second face 28 must be in order to
prevent slipping and bunching during installation .
In the preferred embodiment, the first face 26 has a
coefficient of friction between itself and the floating floor 1 6 less than
0.8, preferably in the range of about 0.4 to ON, and most preferably
about 0.6. The first face 26 must be relatively slippery, compared to
the second face 28, since installation of the floating floor 1 6 generally
consists of sliding the floating floor 1 6 over the first face 26 during
the installation process. The relatively low coefficient of friction of
the first face 26 in contact with the underside of the floating floor 1 6
prevents bunching or tearing of the underlay 1 2 when the floating
floor 1 6 is slid into place during installation .
In the preferred embodiment, the film 1 8 has a tensile
strength of greater than about 2500 psi ( 1 76 kg/cm2) in the machine
direction, an elongation of less than 250% in the machine direction, a
tensile strength of greater than about 2500 psi ( 1 76 kg/cm2) in the
cross-machine direction and elongation of less than 250% in the
cross-machine direction. In the most preferred embodiment, the film
has a tensile strength of about 31 58 psi (222.5 kg/cm2) in the
machine direction, an elongation of less than 222% in the machine
direction, a tensile strength of about 2874 psi (202.1 kg/cm2) in the
cross-machine direction, and a elongation of lass than 231 % in the
cross-machine direction .
In the preferred method of installation of the present
inventive system, the subfloor 1 4 is first prepared by sweeping or
vacuuming in order to remove dirt or other foreign articles that may
tear the underlay 1 2, making it difficult for the underlay 1 2 to grip the
subfloor 1 4, or otherwise cause irregularities in the underlay 1 2 after
installation.
The underlay 1 2 is then laid over the subfloor 1 4 so that
the second face 28 is against the subfloor 1 4. It will be understood
by those in the art that the underlay 1 2 may be manufactured to any
desired dimensions. In the most preferred method, 30 inch (0.76 cm)
wide sheets of the underlay 1 2 are laid on the subfloor 1 4 so that
their edges abut each other. Seams 30, defined by abutting sheets of
underlay 1 2, are then sealed by tape 32 in order to create a moisture
impermeable underlay 1 2. As is mentioned above, if the seams 30
are not taped, moisture may travel horizontally through the foam 20
and migrate up through the seams 30. In the preferred method, the
tape 32 is 2 inches (5 cm) packing tape having a water insoluble
adhesive such as is readily available from the 3M Corporation . It will
be understood by those in the art that any suitable sealant may be
used to fix the sheets of underlay 1 2 in relation to each other and
prevent moisture from the subfloor 1 4 from seeping up through the
seams 30.
When installing the floating floor system 1 0, the underlay
1 2 is laid on the subfloor 1 4 so as to leave the underlay edge 34
riding up a wall 36, as shown in Fig . 2. The floating floor 1 6 is then
slid across the second face 26 of the underlay 1 2 to be located at
any desired position. The underlay edge 34 may be thereafter
trimmed to the room size or concealed by a strip of moulding (not
shown) .
From the above disclosure of the detailed description of
the present invention and the preceding summary of the preferred
embodiment, those skilled in the art will comprehend the various
modifications to which the present invention is susceptible.
Therefore, I desire to be limited only by the scope of the following
claims and equivalents thereof.
I claim: